Product description
User guide
  1.Introduction:
  The fiber grating temperature online monitoring system is mainly for on-line monitoring of parts of the switchgear and transformer that are prone to over-temperature during long-term operation (upper and lower contacts and connectors of the switchgear; transformer windings, iron cores, etc.) to avoid overloading. The resulting temperature is too high and causes unnecessary losses. The product is mainly composed of a fiber optic host, a probe cable, and a fiber grating sensor. Among them, the fiber optic host is responsible for fiber signal processing, alarm and parameter setting, etc. The fiber grating sensor is responsible for temperature collection on site. The fiber optic host can also be connected to the fire alarm controller via RS485/232, CAN, and Ethernet interfaces to form a complete fire alarm system.
 
  2.Structural characteristics and working principle:
  PD-GXGS series products: fire power supply, fiber grating temperature sensitive fire detector, fiber grating sensor, temperature sensing cable or temperature sensing fiber.
  The fiber grating temperature detection system mainly includes: optical path system, photoelectric conversion system, data acquisition and processing system, and data display output device. The light of the light source is transmitted to the external FBG sensor through the optical splitter. The sensor reflects the light of a specific wavelength and transmits it to the photoelectric conversion system through the optical splitter, and converts the optical wavelength signal emitted by the FBG into a photodetector. The electrical signal collects the electrical signal of the photodetector, processes it, and converts the electrical signal into a digital signal. Transfer to the data display output device through the network port or serial port.
 
  3.technical parameters
  Temperature range: -30 °C ~ +120 °C (expandable)
  Alarm mode: constant temperature, differential temperature, differential temperature
  Detection method: point type
  Recovery performance: recoverable
  Function composition: detection alarm type
  Number of channel sensors: up to 16 sensors per channel
  Number of channels: up to 16 channels
  Measurement method: single-ended
  Reflectance: 90%
  Full width at half maximum: 0.7nm
  Side mode suppression ratio: 15dB
  Minimum spacing: 10mm
  Pitch accuracy: 5mm
  Tensile force: 100kpsi
  Fiber type: smf-28
  Connector: none
  Pigtail length: 500mm
  Temperature measurement accuracy: ±1°C (satisfying national standard GB/T21197-2007)
  Temperature resolution: 0.1°C
  Inspection period: ≤30s (satisfying national standard GB/T21197-2007)
  Communication interface: RS232/485, CAN, RJ45, relay
  Fiber type: GI62.5/125, GI50/125
  Optical fiber interface: FC/APC (optional for E2000)
  Host operating temperature: 0°C ~ 40°C
  Host operating humidity: <95% RH
  Working power: 24VDC (220VAC/50Hz optional)
  Maximum power consumption: 50W
We could not find any corresponding parameters, please add them to the properties table

 

Previous
Next
There is currently no content to display
Please add data record on website background.

Other products

Previous page
1
2
4
迪凯光电

400-811-6877

Tel:027-8750 9386   027-8750 9105
Add:Dingye building C block, International Enterprise Center, Optics Valley Avenue, Wuhan China  
Fax:027-87745185   
Mail:dkoe@chinadikai.com